Performance Optimization and Water-Saving Retrofit of the Sealing Water Cooling System for Unit 1 Feedwater Pumps at PLTU IPP Sumsel

Authors

  • Wang Zhiliang PT Datang DSSP Power Indonesia, Indonesia

DOI:

https://doi.org/10.58344/jws.v4i12.1600

Keywords:

Feed water pumps, Sealed water coolers, System upgrades, Chilled water, Water conservation optimization

Abstract

During the operation of Unit 1 at PLTU Sumsel 5, the feedwater pump seal water cooler experienced issues such as poor cooling performance, low heat exchange efficiency, and high-water consumption, leading to elevated equipment operating temperatures, increased energy consumption, and wastage of water resources. To enhance the operational economy and reliability of the equipment, an optimization upgrade was carried out on the existing seal water cooling system during the unit's annual maintenance. The retrofit plan involved replacing the originally used demineralized water-cooling source with chilled water from the HVAC system as the working medium, while retaining the demineralized water system as a backup source. After the upgrade, the system's cooling performance improved significantly, with a reduction of approximately 65% in cooling water consumption. This achievement demonstrates dual benefits of water conservation and reduced energy consumption, while also improving operational efficiency. The project provides replicable engineering experience for optimizing auxiliary systems in similar units.

Downloads

Published

2025-12-31

How to Cite

Zhiliang, W. (2025). Performance Optimization and Water-Saving Retrofit of the Sealing Water Cooling System for Unit 1 Feedwater Pumps at PLTU IPP Sumsel. Journal of World Science, 4(12), 1771–1777. https://doi.org/10.58344/jws.v4i12.1600